Pemetaan Statistik Estimasi Kuat Tekan Beton Kolom Eksisting pada Tiga Lantai Menggunakan Rebound Hammer Test
DOI:
https://doi.org/10.51158/v6xgrw36Keywords:
Existing Concrete, Rebound Hammer, Concrete Compressive Strength, Coefficient of Variation, Non-destructive TestingAbstract
Evaluating the quality of existing concrete in column elements is essential for assessing the actual structural condition of operational buildings, particularly when destructive testing is impractical. This study evaluates the quality of existing concrete columns in the Campus 2 Building of Politeknik Pekerjaan Umum, Semarang City, using a Type N Rebound Hammer Test as a non-destructive testing (NDT) method. Testing was conducted on the Ground Floor, 3rd Floor, and 5th Floor, covering three columns with nine test points per column, resulting in 81 test points. A quantitative descriptive-analytical method was employed by converting rebound numbers into estimated concrete compressive strength (f'c) using a polynomial regression equation for the Type N hammer. Statistical analyses were performed using the mean, standard deviation, and coefficient of variation (CV), referring to the ACI 228.1R-19 criteria. The results indicate that the estimated compressive strength ranges from 22.00 to 26.64 MPa, with CV values below 10% for all columns and floors, classified as very good. However, the 5th Floor exhibits greater variation (CV of 8.78%). A total of 7 out of 9 columns (77.8%) meet the preliminary evaluation criteria, while two columns on the 5th Floor require further assessment. The rebound hammer method provides preliminary information on concrete uniformity without disrupting building operations, although further verification is necessary.